Application and Functions

CP 930 Condutivity Probe is for mounting in to the boiler
directly. BC 910/BC 915 Contech Controller measures
the conductivity of the boiler water continuously. This
measured value is compared with the set point in the
controller. If it is lower than the set point the blowdown
valve remains closed. If the measured value is higher
than the set point the controller keeps open the blow
down valve until the measured value drops below the
set point.

BCS 935 Contech Conductivity Control System consist
of BC 910/BC 915 Blowdown Controller, CP 930 Conductivity
Probe and BCV 900 Blowdown Control Valve.

When TDS is low, valve simply remains closed.
No unnecessary losses, saves water treatment and chemical costs. Also it reduces water consumption and effluent
disposal charges. Conductivity measurement with automatic temperature compensation provides accurate TDS control.

Technical Data

Type                                              : BCS 930
Control Characteristics         :Conductivity Monitoring and Control
Nominal Pressure            : PN 25/40
Max. Çalışma Basıncı    : 32 bar (g)
Max. Çalışma Sıcaklığı  : 239 °C
Functions                           : Alarm Testi, Vana Testi, Alarm Reset, 4-20 mA iletkenlik bilgi çıkışı ve Modbus RS 485 iletişim

Files

Catalog Technical Data