Application and Functions

The CCS 990 Condensate Contamination Control System consists of the BC 900 Blowdown Controller, the CP 910 Conductivity Sensor and Control Valves.

The condensate that returns to the boiler room from the steam/condensate system is sent back to the condensate tank to be used as feed water in the steam boiler.

The condensate detection system monitors and displays the conductivity of the condensate. If the conductivity value of the returning condensate rises above a predetermined value, it automatically directs the condensate to the discharge instead of returning to the boiler system/condensate tank.

If the conductivity value is below the specified value, it is allowed to return the condensate to the condensate tank.

Technical Data

Type Features                          : Conductivity check, high conductivity alarm
Nominal Pressure                    :
PN 40
Max. Working Pressure           :
32 bar (g)
Max. Operating Temperature :
239 °C
Functions                                :
Alarm Test, Valve Test, Alarm Reset, 4-20 mA conductivity information output and Modbus RS 485 communication

Files

Catalog Technical Data