Application and Functions
CP 930 Condutivity Probe is for mounting in to the boiler
directly. BC 900 Smart Controller measures the conductivity
of the boiler water continuously. This measured value
is compared with the set point in the controller. If it is
lower than the set point the blowdown valve remains
closed. If the measured value is higher than the set
point the controller keeps open the blow down valve
until the measured value drops below the set point.
BCS 930 Smart Conductivity Control System consist
of BC 900 Blowdown Controller, CP 930 Conductivity
Probe and BCV 900 Blowdown Control Valve.
When TDS is low, valve simply remains closed. No unnecessary
losses, saves water treatment and chemical costs. Also it
reduces water consumption and effluent disposal charges.
Conductivity measurement with automatic temperature compensation provides accurate TDS control.
Technical Data
Type : BCS 930
Control Characteristics :Conductivit Monitoring and Control
Nominal Pressure : PN 25/40
Max. Çalışma Basıncı : 32 bar (g)
Max. Çalışma Sıcaklığı : 239 °C
Functions : Alarm Testi, Vana Testi, Alarm Reset, 4-20 mA iletkenlik bilgi çıkışı ve Modbus RS 485 iletişim